      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • Referenties
  • Over Stöbich
  • Wereldmarktleider
  • Duurzaamheid
  • Actueel
  • Contact

SYSTEEM: GCC

GCC

Productbeschrijving

Enkelblads, verticaal en horizontaal sluitende brandbeveiliging voor wandopeningen van railgebonden transportsystemen. Transportsystemen; gescheiden en niet-gescheiden transportsystemen in de afsluitzone.

Type constructieBrandwerende afsluiting in de loop van spoorgebonden transportsystemen
Bewijs van bruikbaarheidETA-16/0851 Europese technische beoordeling | VKF Technische informatie Nr. 32235
Richting van sluitingvan boven naar beneden | van links naar rechts | van rechts naar links
BrandweerstandEI1 90 | getest volgens DIN EN 1366-7:2004 | geclassificeerd volgens EN 13501-2:2007
SluitingscycliC4 | Aantal sluitcycli 100.000 | Verticale sluitrichting
C5 | Aantal sluitcycli 200.000 | horizontale sluitrichting
Heropening gemotoriseerd
TransportsysteemOnonderbroken transportsysteem | Hellend transportsysteem | Continu bandtransportsysteem | Continue Continue hangkettingbaantechnologie | Continue rollenbaantechnologie | Continue transportbandtechnologie
Zichtbare oppervlakkenVerankeringsdelen:
gegalvaniseerd | gecoat in RAL-kleur | roestvrij staal 1.4301 (V2A)

Festpaneel en klepblad:
onbehandelde brandwerende platen | geverfd met dispersieverf in een vergelijkbare RAL-kleur | verzinkte plaatstalen beplating | plaatstalen beplating roestvrij staal 1.4301 (V2A) | plaatstalen beplating gecoat in RAL-kleur

Afmetingen en systeemontwerp

Door de combinatie van indelingen of de verhouding tussen de vrije systeembreedte en de vrije systeemhoogte kunnen de opgegeven maximumafmetingen kleiner zijn en kunnen de afmetingen van de kast en de geleiderails variëren. De details op de offerte zijn van toepassing.

Component (dragende structuur) waarin de sluiting kan worden geïnstalleerdBeschikbare brandwerendheidsklasse
Klare wandopening
grootste breedte LBgrootste hoogte LHGrootste oppervlakte
Stevige wand met hoge dichtheid, metselwerk of massief beton met
totale dichtheid van ≥ 800 kg/m3 en een dikte ≥ 150 mm
EI1 90
EI2 90
3.600 mm4.200 mm10,0 m2
Lage dichtheid massieve wand, cellenbeton met totale dichtheid
van ≥ 450 kg/m3 en een dikte ≥ 150 mm
EI1 90
EI2 90
3.600 mm4.200 mm10,0 m2


De inbouwsituatie moet voldoen aan de bouwvoorschriften van het land van inbouw. De brandwerendheid van een plafond- of wanddraagconstructie en de aangrenzende bouwdelen moet ten minste overeenkomen met die van de brand- en/of rookwerende afsluiting/brand- en/of rookwerend gordijn. De stabiliteit en bruikbaarheid van de aangrenzende wanden en onderdelen moeten worden aangetoond onder algemene omgevingsomstandigheden en in geval van brand. Zie ook de opmerkingen over de standaard draagconstructie in EN1366-7:2004 of EN1363-1:2020. Het brandbeveiligingssysteem mag ook in geval van brand niet worden blootgesteld aan andere belastingen dan zijn eigen gewicht.

Ontwerp van structurele systemen (verticaal)

Fibershield-I
a = 155 | c = 570 | f = 70 | s = 51

Ontwerp van structurele systemen (horizontaal)

Fibershield-I
b = 260 | c = 270 | d = 500 | f = 70 | i = 425 | s = 51