    • Fire protection curtains

      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • Pověření
  • Tematické světy
  • Světový lídr
  • Udržitelnost
  • Zprávy
  • Kontakt

SYSTÉM: GCC

GCC

Popis produktu

Jednokřídlý, vertikálně a horizontálně uzavíratelný protipožární uzávěr pro stěnové otvory kolejnicových dopravních systémů. Dopravníkové systémy; samostatné a nesamostatné dopravníkové systémy v oblasti uzávěru.

Typ konstrukcePožární uzávěr v průběhu dopravních systémů vázaných na železnici
Důkaz použitelnostiETA-16/0851 Evropské technické posouzení | VKF Technické informace Nr. 32235
Směr uzavřeníZhora dolů | zleva doprava | zprava doleva
Odolnost proti ohniEI1 90 | testováno podle DIN EN 1366-7:2004 | klasifikováno podle EN 13501-2:2007
Zavírací cyklyC4 | Počet zavíracích cyklů 100 000 | Vertikální směr zavírání
C5 | Počet uzavíracích cyklů 200 000 | horizontální směr zavírání
Otvírání motorizované
Dopravní systémPřerušovaný dopravní systém | Šikmý dopravní systém | Pásový dopravní systém | Kontinuální dopravní systém | Kontinuální pojezdový dopravník | Technologie kontinuálního závěsného řetězového dopravníku | Technologie kontinuálního válečkového dopravníku | Technologie kontinuálního dopravníku
Viditelné plochyPřídavné části:
pozinkované | s povrchovou úpravou v barvě RAL | nerezová ocel 1.4301 (V2A)

Plášť a list klapky:
neošetřené protipožární desky | natřené disperzní barvou v podobné barvě RAL | opláštění z pozinkovaného plechu | opláštění z nerezové oceli 1.4301 (V2A) | opláštění z plechu s povrchovou úpravou v barvě RAL

Rozměry a konstrukce systému

Kombinace klasifikací nebo poměr světlé šířky systému a světlé výšky systému může snížit uvedené maximální rozměry a rozměry skříně a vodicích lišt se mohou lišit. Platí údaje uvedené v nabídce.

Komponent (nosná konstrukce), do kterého může být uzávěr instalovánDosažitelná třída požární odolnosti
průhledný otvor ve stěně
největší šířka LBnejvětší výška LHnejvětší plocha
Pevná stěna s vysokou hustotou, zděná nebo plná betonová s
celkovou hustotou ≥ 800 kg/m3 a tloušťkou ≥ 150 mm
EI1 90
EI2 90
3.600 mm4.200 mm10,0 m2
Pevná stěna s nízkou hustotou, pórobeton o celkové hustotě
s hustotou ≥ 450 kg/m3 a tloušťkou ≥ 150 mm
EI1 90
EI2 90
3.600 mm4.200 mm10,0 m2


Instalační situace musí odpovídat požadavkům stavebních předpisů země instalace. Požární odolnost nosné konstrukce stropu nebo stěny a přilehlých stavebních prvků musí odpovídat minimálně požární odolnosti požárního a/nebo kouřotěsného uzávěru/požárního a/nebo kouřotěsného závěsu. Musí být prokázána stabilita a provozuschopnost přilehlých stěn a konstrukčních prvků za obecných okolních podmínek a v případě požáru. Viz také poznámky ke standardní nosné konstrukci v normě EN1366-7:2004 nebo EN1363-1:2020. Protipožární systém nesmí být ani v případě požáru vystaven žádnému dalšímu zatížení kromě vlastní hmotnosti.

Návrh konstrukčního systému (vertikální)

Fibershield-I
a = 155 | c = 570 | f = 70 | s = 51

Návrh konstrukčního systému (horizontální)

Fibershield-I
b = 260 | c = 270 | d = 500 | f = 70 | i = 425 | s = 51