• EN
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • References
  • Theme worlds
  • World market leader
  • Sustainability
  • News
  • Contact
Product - Supercoil

Supercoil

The conventional smoke apron for high demands and large dimensions

Product description

Supercoil is outstanding for its flexibility in the implementation of made-to-measure solutions. The smoke apron consists of one web part up to 50 m in width and features a drop length of 9.5 m. It is designed for high time classes at temperature loads up to 600 0C (D) and 1,100°C (ETK curve - DH). If guide rails are used, the smoke apron ensures that zero smoke escapes over the entire width of the apron. Thanks to the 'Gravigen' drive motor the apron closes without external energy. Supercoil is also suitable as a floor-closing and partition-forming smoke apron and can be equipped with an opening that allows persons to pass. Furthermore, the clever design allows for a combination with the passable Stripecoil smoke apron.

Supercoil

Type

Textile smoke apron

Proof of usability

CE according to DIN EN 12101-1 • UL 1784

Fabric

Protex 600.1 A2 • Protex 1100.1 A2

Verification

0761-CPD-0060

Closing direction

From top to bottom

Closing cycles

1,000 cycles according to DIN EN 12101-1

Classification

DH 120 • D 60 • Classification according to DIN EN 12101-1

Triggering

Approved hold-open system • To be provided on site

  • Supercoil
  • Supercoil
  • Supercoil
  • Supercoil
Constructive system design - With guide rail

1Smoke detector2Casing3side guides4Fixing bracket5Fabric6Closing element7Tubular motor8Control module9Control with operating unit10Manual release11Wicket door (optional)


1Smoke detector2Casing3side guides4Fixing bracket5Fabric6Closing element7Tubular motor8Control module9Control with operating unit10Manual release11Wicket door (optional)

Fabric

System width

Drop length

t (mm)

h (mm)

Protex 600.1 A2 / 1100.1 A2

≥ 0.8 m - ≤ 1.6

≤ 3.5 m

190

250

Protex 600.1 A2 / 1100.1 A2

> 1.6 m - ≤ 30 m

≤ 3.5 m

190

200

Protex 600.1 A2 / 1100.1 A2

≥ 1,2 m ≤ 30 m

> 3.5 m - ≤ 6 m

190

250

Protex 1100.1 A2

≥ 2.0 m ≤ 20 m

> 6 m - ≤ 9 m

235

290

Constructive system design - Without guide rail

1Smoke detector2Casing4Fixing bracket5Fabric6Closing element7Tubular motor8Control module9Control with operating unit10Manual release


1Smoke detector2Casing4Fixing bracket5Fabric6Closing element7Tubular motor8Control module9Control with operating unit10Manual release

Fabric

System width

Drop length

t (mm)

h (mm)

Protex 600.1 A2 / 1100.1 A2

≥ 0.8 m - ≤ 1.6

≤ 3.5 m

190

250

Protex 600.1 A2 / 1100.1 A2

> 1.6 m - ≤ 50 m

≤ 3.5 m

190

200

Protex 600.1 A2 / 1100.1 A2

≥ 1,2 m ≤ 50 m

> 3.5 m - ≤ 6 m

190

250

Protex 1100.1 A2

≥ 2.0 m - ≤ 50 m

> 6 m - ≤ 9 m

235

290

Closing strips

Standard

Standard

Closing strips - Standard

Type4,6

Special

Spring-loaded closing strip

 - Spring-loaded closing strip

Type4,6 F (Special)

Spring-loaded closing strip

 - Spring-loaded closing strip

Type3,84 F (Special)

Casing installation options

Wall mounting

Ceiling mounting

Suspension mounting

Guide rails

Standard

Type 105 E (embrasure)

Guide rails - Type 105 E (embrasure)

a105 mmb74 mmAL≤ 6 mA≤ 50 m²

Type 105 E (niche)

Guide rails - Type 105 E (niche)

a105 mmb74 mmAL≤ 6 mA≤ 50 m²

Type 105 E(Wall)

Guide rails - Type 105 E(Wall)

a105 mmb74 mmAL≤ 6 mA≤ 50 m²

Type 80 E

Guide rails - Type 80 E

a80 mmb74 mmAL≤ 3,5 mA≤ 18 m²

Type 160 E

Guide rails - Type 160 E

a160 mmb100 mmAL≤ 9 mA≤ 120 m²

References

Product - Olympic Swimming Hall, Munich

Olympic Swimming Hall, Munich

Product - Westfield Mall | Leidschendam, Netherlands

Westfield Mall | Leidschendam, Netherlands

Product - Deutsche Bank Park | Frankfurt am Main, Germany

Deutsche Bank Park | Frankfurt am Main, Germany