• US
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

      • Stoebich Fire & Smoke Curtain P
      • Stoebich Fire & Smoke Curtain E
      • Stoebich Fire & Smoke Curtain HC
      • Stoebich Fire & Smoke Curtain S
      • Stoebich Fire Curtain F
    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

      • ECClos®-S
      • ECClos®-Q
      • ECClos®-FLEX
      • ECClos®-D
      • ECClos®-K
      • Universal-B
      • Omnicompact
      • Universal-S
      • ECClos®-FLEX-S
      • Turbocoil
      • GCC
      • Model RGT
    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

      • Stoebich Smoke Curtain P
      • Stoebich Smoke Curtain M
      • Stoebich Smoke Curtain X
      • Stoebich Smoke Curtain S
      • Fixed smoke curtain
      • Stoebich Smoke Curtain GX
    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

      • Stoebich Smoke Curtain T
      • Stoebich Smoke Curtain H
    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

      • Ecotube
      • Omnitube
    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

      • RZ7
      • RZ3/4
      • RZ8
      • Battery system
      • MoviPower 340/540
      • UPS
  • References
  • Theme worlds
  • News
  • Contact

Stoebich Fire & Smoke Curtain E

Fibershield-E

Product description

In the event of an alarm, self-closing non-thermally insulating fire curtain in vertical installation position and closing direction with small winding housing and guide rails.

TypeNon-insulating fire curtain
VerificationCE marking according to EN 16034:2014 in conjunction with EN 13241:2003+A2:2016
Closing directionFrom top to bottom
Fire resistanceE 30 – EW 90 | Tested according to EN 1634-1:2014+A1:2018 | Classified according to EN 135012:2016
Closing cyclesC0, C, C1, C2 | Tested according to EN 12605:2000-08 and EN 12604:2017-12 | Classified according to EN 13501-2:2016
Fire behaviour of textileA2-s1, d0; B-s1, d0; E-d2 | Tested according to ISO 1716 and EN 13823 or ISO 11295-2 | Classified according to EN 13501-1:2018
Environmental conditionsSpecial environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.).
Visible surfacesgalvanised, RAL - smooth - silk-gloss - standard colour, NCS - standard colour
Fibershield-E

Legend System components:
1 = Smoke detector
2 = Winding case
3 = Guide rail
4 = Control module
5 = Trigger device (see the valid general type approval of the brake system for design details of the electrical components.)

Legend Dimensioning
Structure
q = Clear shell construction height
x = Clear shell construction width
System
s = System height
r = Clear system height
y = Clear system width
z = System width
Winding case
t = Depth
h = Height
Guide rail
a = Width
b = Depth
b = Cover

Structural system design (system drawing)

The combination of classifications or the ratio of clear system width to clear system height can reduce the stated maximum dimensions, the dimensions of the winding enclosure and the guide rails can vary. The specifications on the offer apply.

ClassificationFabricSystem width (SB)Drop length (AL)t (mm)h (mm)
E 303350 x 2815Ecotex 1100 A2140Type A, BType 1, 2
E 603350 x 2815Ecotex 1100 A2140Type A, BType 1, 2
E 903350 x 2815Ecotex 1100 A2200Type A, BType 1, 2
EW 303350 x 2815Ecotex 1100 A2140Type A, BType 1, 2
E 306800 x 6800Heliotex140Type A, BType 1, 2
E 906000 x 6000Heliotex200Type A, BType 1, 2
EW 906000 x 6000Heliotex200Type A, BType 1, 2
C06000 x 6000Heliotex
C0, C1, C25880 x 4280Ecotex 1100 A2

The installation situation must comply with the building code requirements of the country of installation. The fire resistance of a ceiling or wall support structure and the adjacent components must at least correspond to that of the fire and/or smoke protection closure/fire and/or smoke protection curtain. Proof of the stability and serviceability of the adjacent walls and components must be provided under general ambient conditions and in the event of fire. See also notes on the standard supporting structure in EN1366-7:2004 or EN1363-1:2020. The fire protection system must not be subjected to any additional loads other than its own weight, even in the event of fire.
* Deviations from size dimensions on request
** Tested wall types according to the installation instructions

Winding case


Deckenmontage
Ceiling mounting
Type A: t = 200 mm, h = 220 mm
Type B: t = 250 mm, h = 260 mm
Wandmontage
Wall mounting
Type B: t = 200 mm, h = 220 mm
Type C: t = 250 mm, h = 260 mm
Deckenmontage Unterdecke
Ceiling mounting suspended ceiling
Type B: t = 200 mm, h = 220 mm
Type C: t = 250 mm, h = 260 mm

Guide rails


Typ 1
Type 1(Wall mounting)
a = 80 mm

b = 60 mm
c ≥ 0 mm
FSV-E-80-KB
Type 2 (Soffit mounting)
a = 80 mm
b = 60 mm
FSV-E-80-KN
Type 2 (Niche mounting)
a = 80 mm
b = 60 mm

aN = 85 mm
bN = 70 mm