• US
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • References
  • Theme worlds
  • News
  • Contact

Stoebich Fire & Smoke Curtain S

  • Fibershield-S

Product description

Fire protection that leads around corners: The floor space of the closure can be realised in a rectangular and polygon-shape with angles between 30° and 150°. No support elements are required despite the corner design. In addition to a closed polygon shape, open systems can also be realised that close against the wall by installing special guide rails. The fire protection curtain can be closed without any external energy by means of the 'Gravigen' drive system that is included as standard. The Stoebich Fire & Smoke Curtain S complex allows for complex sealing geometries to be realised, while also complying with the requirement of closing off a space for more than 90 minutes.

Construction typeTextile fire protection curtain
Executable protection targetEW 90
FabricFire & Smoke Fabric E | Stoebich Fire & Smoke Fabric H
ProofIBS 08062416 | UL 10D | UL 10 (b) (2009) | UL 10 (c) (2009) | UL 10 (d) (2009) | NFPA 252 (2012)
Closing directionFrom top to bottom
Fire resistance2 hours fire rating according to UL 10D, 20 minutes fire rating according to UL 10B, UL 10C, NFPA 252
Closing cyclesC1 number of closing cycles 500
STOEBICH FIRE & SMOKE CURTAIN S

Legend system components:
1 = Smoke detector
2 = Casing
3 = Side guids
4 = Tubular motor
5 = Fabric
6 = Closing element
7 = Coil
8 = Control module
9 = Control with operating unit
10 = Manual release
SL = System length

Constructive system design (System drawing)

Fabric System widthDrop length (AL)t (mm)h (mm)
Ecotex 1100 A2< 50 m< 3 m490125
Ecotex 1100 A2< 50 m> 3 m - ≤ 6 m490225
Heliotex 9 EW 90< 50 m≤ 2,2 m490125
Heliotex 9 EW 90< 50 m> 2,2 m - ≤ 4,5 m490225
Heliotex 9 EW 90< 50 m> 4,5 m - ≤ 6 m490450

Bottom Bar


Closing strips Fibershield-S
Standard
Closing strips Fibershield-S
Special
With light spots or light strip

Casing Standard


Fibershield-S Gehäuse
Casing (open)
h = from table
t = 490 mm

d = 290 mm
Fibershield-S Gehäuse
Casing (closed)
h = from table
t = 490 mm

d = 290 mm

Casing Special


Fibershield-S Casing
Casing EI (open)
h = 240 mm
t = 490 mm

d = 290 mm
Fibershield-S Casing
Casing EI (closed)
h = 240 mm
t = 600 mm

d = 560 mm
Fibershield-S Casing
Locking equipment (optional)
h = 125 mm
t = 490 mm

d = 290 mm
S = Infrared security

Side guides


Guide for open polygons
Guide for open polygons
a = 117 mm
b = 278 mm