Stoebich Fire & Smoke Curtain S
| Function | Textile fire protection curtain |
| Executable protection target | EW 90 |
| Fabric | Fire & Smoke Fabric E | Stoebich Fire & Smoke Fabric H |
| Proof | IBS 08062416 | UL 10D | UL 10 (b) (2009) | UL 10 (c) (2009) | UL 10 (d) (2009) | NFPA 252 (2012) |
| Closing direction | From top to bottom |
| Fire resistance | 2 hours fire rating according to UL 10D, 20 minutes fire rating according to UL 10B, UL 10C, NFPA 252 |
| Closing cycles | C1 number of closing cycles 500 |
* Angle specifications: Complete range min. 30° to max. 179°
Angle specifications (standard):
The minimum standard angle is 65°, the maximum standard angle is 165°. These specifications refer to external angles and internal angles with Ecotex 1100 A2 and Heliotex 9 fabrics.
Angle specifications (special):
The maximum special angle can be up to 179° (only with Ecotex 1100 A2).
Restriction for angles below 65°:
1) Angles below 65° must be broken down into a 90° angle and an obtuse angle. The standard construction can be used here.
2) Notwithstanding point 1, a special construction must be requested.
Dimensions and system structure
The combination of classifications or the ratio of clear system width to clear system height may reduce the maximum dimensions specified, and the dimensions of the housing and guide rails may vary. The information provided in the offer applies.
| Fabric | System width | Drop length (AL) | t (mm) | h (mm) |
| Ecotex 1100 A2 | < 50 m | < 3 m | 490 | 125 |
| Ecotex 1100 A2 | < 50 m | > 3 m - ≤ 6 m | 490 | 225 |
| Heliotex 9 EW 90 | < 50 m | ≤ 2,2 m | 490 | 125 |
| Heliotex 9 EW 90 | < 50 m | > 2,2 m - ≤ 4,5 m | 490 | 225 |
| Heliotex 9 EW 90 | < 50 m | > 4,5 m - ≤ 6 m | 490 | 450 |
The installation situation must comply with the building regulations of the country of installation. The fire resistance of a ceiling or wall support structure and the adjacent components must be at least equal to that of the fire and/or smoke protection barrier/fire and/or smoke protection curtain. The stability and serviceability of the adjacent walls and components must be verified under normal environmental conditions and in the event of a fire. See also notes on standard supporting structures in EN1366-7:2004 and EN1363-1:2020. Even in the event of a fire, the fire protection system must not be exposed to any additional load other than its own weight.
Deviations from standard dimensions available on request.