SYSTEM: OMNICOMPACT-CSC

Omnicompact-FAA

Product description

In the event of an alarm, self-closing, fire-resistant fire protection closure in the design of a lift-and-slide door with separate conveyor technology.

TypeFire protection closure in the course of separate conveyor systems in the design of a lift-and-slide gate
CertificationGeneral type approval Z-6.22-2664; in accordance with EN 16034:2014 in conjunction with EN 13241:2003+A2:2016
Closing directionfrom top to bottom
Fire resistanceEI2 90 | tested in accordance with EN 1634-1:2014-03 | classified in accordance with EN 13501-2:2023
Closing cyclesC2 | tested in accordance with EN 12605:2000-08 | classified in accordance with EN 13501-2:2023
Environmental conditionsNot considered are special environmental conditions (e.g. humidity > 80%, ambient temperature < 5 °C and > 45 °C, wind loads, etc.)
Visible surfaces of the housing and guide railsGalvanised | RAL - smooth - silk gloss - standard colour shade | NCS - standard colour shade
Omnicompact-FAA

Legendary system components:
1 = Smoke detector
2 = Guide rails
3 = Mounting bracket
4 = Slat
5 = End element
6 = Drive motor
7 = Control with operating unit
8 = Manual release optional (manual release required if the control with operating unit is higher than 1.4 m above the upper edge of the finished floor)

.

Legal dimensioning:
Body
q = clear unfinished height
x = clear unfinished width
System
s = system height
y = clear system width
z = system width
Housing
t = depth
t1 = Console
t2 = Space requirement control box ceiling
h = Height
v = Offset between guide rail and winding housing
Guide rail
a = width
b = depth
Conveyor system
f = Separation point width (>107 mm)

Size dimensions and system structure

The dimensions of the brackets and guide rails may vary. The information provided in the quotation applies.

Fire resistance classSize max.* [x x q] in mmFabric/componentWall thickness** in mmConsoleGuide rails
EI2 906000 x 5600Lamella≥ 240A, B, CType 1
C26000 x 5600Lamella


The installation situation must comply with the building code requirements of the country of installation. The fire resistance of a ceiling or wall support structure and the adjoining components must at least correspond to that of the fire and/or smoke protection closure/fire and/or smoke protection curtain. Proof of the stability and serviceability of the adjacent walls and components must be provided under general ambient conditions and in the event of fire. See also notes on the standard supporting structure in EN 1366-7:2004 or EN 1363-1:2020. The fire protection system must not be subjected to any additional load apart from its own weight, even in the event of fire.
* Deviations from size dimensions on request
** tested wall types according to the installation instructions

Console


Omnicompact
Overlapping lintel and vertical sealing frame with bracket
Type A
Omnicompact
Suspension of drive shaft with clear structural width > 4500 mm via gallows
Type B
Omnicompact
Suspension of drive shaft with clear unfinished width > 4500 mm above ceiling
Type C

Guide rails


Omnicompact-FAA
Typ 1
Omnicompact-FAA