      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • Pověření
  • Tematické světy
  • Světový lídr
  • Udržitelnost
  • Zprávy
  • Kontakt

SUPERCOIL

  • Supercoil

Popis produktu

Supercoil se vyznačuje svou flexibilitou při implementaci řešení na míru. Kouřová zástěna je vyrobena z jednoho kusu do 50 m šířky a do 9,5 m rolovací výšky a je vhodná pro vysoké časové třídy při teplotních zátěžích až do 600 0C (D) a 1.100°C (ETK-křivky- DH). Při použití vodících lišt lze dosáhnout u celé kouřové zástěny 0% propustnosti. Systém je uzavírán bez potřeby cizí energie, a to pohonným systémem „Gravigen“. Supercoil je určený také k uzavírání až k podlaze a k vytváření prostorů, nicméně ho lze integrací prokluzovacích dveří využít i pro průchod osob. Mimoto nabízí sofistikovaná konstrukce možnost kombinace s průchozí automatickou kouřovou zástěnou Stripecoil.

KonstrukceTextilní kouřové zástěny
Doklad o použitelnosti CE podle DIN EN 12101-1 | UL 1784
TkaninaProtex 600.1 A2 | Protex 1100.1 A2
Doklad0761-CPD-0060
Směr uzavíráníz vrchu dolů
Uzavírací cykly1000 cyklů podle DIN EN 12101-1
KlasifikaceDH 120 | D 60 | klasifikace podle DIN EN 12101-1
SpouštěníSchválené FSA | na straně budovy

Konstrukční provedení systému (s vodicí lištou)

Supercoil

Komponenty systému Legend:
1 = Detektor kouře
2 = Kastlík
3 = Vodící lišta
4 = Upevňovací konzole
5 = Tkanina
6 = Ukončovací lišta
7 = Trubkový motor
8 = Řídící modul
9 = Ovládání
10 = Tlačítko
11 = Vstupní dveře (volitelné)

TkaninaŠířka systému (SB)Rolovací výška (AL)t (mm)h (mm)
Protex 600.1 A2 / 1100.1 A2≥ 0,8 m - ≤ 1,6 m≤ 3,5 m190250
Protex 600.1 A2 / 1100.1 A2≥ 1,6 m - ≤ 30 m≤ 3,5 m190200
Protex 600.1 A2 / 1100.1 A2≥ 1,2 m - ≤ 30 m> 3,5 m - ≤ 6 m190250
Protex 1100.1 A2≥ 2,0 m - ≤ 20 m> 6 m - ≤ 9 m235290

Konstrukční provedení systému (bez vodicí lišty)

Supercoil

Komponenty systému Legend:
1 = Detektor kouře
2 = Kastlík
4 = Upevňovací konzole
5 = Tkanina
6 = Ukončovací lišta
7 = Trubkový motor
8 = Řídící modul
9 = Ovládání
10 = Tlačítko

TkaninaŠířka systému (SB)Rolovací výška (AL)t (mm)h (mm)
Protex 600.1 A2 / 1100.1 A2≥ 0,8 m - ≤ 1,6 m≤ 3,5 m190250
Protex 600.1 A2 / 1100.1 A2≥ 1,6 m - ≤ 50 m≤ 3,5 m190200
Protex 600.1 A2 / 1100.1 A2≥ 1,2 m - ≤ 50 m> 3,5 m - ≤ 6 m190250
Protex 1100.1 A2≥ 2,0 m - ≤ 50 m> 6 m - ≤ 9 m235290

Ukončovací lišty


Ukončovací lišty Fibershield-P
Standardní
Typ 4,6
Ukončovací lišty Fibershield-P
Pružinová ukončovací lišta
Typ = 3,84 F (Sonder)
Ukončovací lišty Fibershield-P
Pružinová ukončovací lišta
Typ = 4,6 F (Sonder)

Varianty montáže skříně


Montáž na stěně
Montáž na stěně
Na zavěšení
Na zavěšení
Montáž na stropě
Montáž na stropě

Vodící lišty


Typ 105 E (Nika)
Typ 105 E (Nika)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²
Typ 105 E (Ostění)
Typ 105 E (ostění)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²
Typ 105 E (stěna)
Typ 105 E (Stěna)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²


Typ 80 E
Typ 80 E
a = 80 mm
b = 74 mm

AL = ≤ 3,5 m
A = ≤ 18 m²
Typ 160 E
Typ 160 E
a = 160 mm
b = 100 mm

AL = ≤ 9 m
A = ≤ 120 m²