      Fire protection curtains

      Fire protection curtains are seal openings in walls and ceilings in case of fire. The constructional set-up (rolling- or folding technology) and the use of different fabrics offer a wide application spectrum as well as different protection targets or classifications and time classes. Casings and side guides of those flexible applicable systems are integrated almost invisibly in the building and provide much scope for design of sophisticated architecture for opened designs.

    • Conveyor system closures

      Conveyor system closures

      Manifold production - and logisitc processes require different construction types of conveying systems. If the haulage drifts are passing through fire-retarding resp. fire-resisting walls or ceilings, the necessary openings must be provided with fire protection closures to avoid the expansion of the fire by conveyor technique or by conveyed material. In case of fire the conveyor system closures have to seal those openings immediately and automatically. Thereby a classified fire resistance as well as the smoothly clearing of the closing area must be respected in case of release.

    • Smoke curtains

      Smoke curtains

      A smoke curtain is part of unit keeping areas free from smoke and may include building parts like natural smoke and heat venting systems and automatic smoke and heat venting systems. Smoke curtains restrict the movement of fire gases inside a building in case of fire.

    • Smoke protection closures

      Smoke protection closures

      In closed condition smoke protection closures restrict the passage of smoke in the phase of fire formation so as to enable the rescue of people, animals or materials assets in case of a fire in the room positioned behind it without the need of breathing protection.

    • Tube sealings

      Tube sealings

      The solution to problems with fire protection dampers for ventilation and air conditioning systems in conveying processes. Stöbich offers fire protection for pneumatic conveying lines where the closing elements are not exposed to the flow. Thus, damage or contamination of the closure element is avoided by abrasive conveyed goods.

    • Controls

      Controls

      Control systems are necessary for all automatic fire protection systems! They are safety-relevant, because without their function or in the event of a malfunction, the entire investment of a fire protection partition would be useless. Controllers coordinate both fire detection and the interaction with other controls, like superordinate building control or the retraction of the closing area at conveyor closing area.

    • Médiathèque Charles Nègre | Grasse, France

      Médiathèque Charles Nègre | Grasse, France

      The Médiathèque Charles Nègre in Grasse, France, is an impressive example of contemporary architecture that reflects the cultural and historical importance of the region. The information center with space for education, culture and encounters was opened in 2011 and designed by the renowned French architecture firm Marc Barani. The building combines modern aesthetics with the traditional architecture of Provence, creating a harmonious link between old and new, for example by combining modern materials such as glass and steel with local natural stone. The generous window fronts create an atmosphere flooded with light. Ecological sustainability is achieved through natural ventilation and the resulting reduction in energy consumption; green spaces are also integrated on various levels. Our <a href="/us/solutions/fire-protection-curtains/stoebich-fire-smoke-curtain-hc"><b>➥ horizontal Fire and smoke curtain hc</b></a> fire protection curtains fit perfectly into this marvel of contemporary architecture. They securely close the ceiling openings in the event of a fire, but otherwise remain invisible and let in plenty of light and air. Copyright attribution: © Ivry Serres

  • References
  • Theme worlds
  • World market leader
  • Sustainability
  • News
  • Contact

SYSTEM: FIBERSHIELD® | MODEL: FIBERSEAL

  • Fiberseal

Product description

In case of an alarm, self-closing smoke protection closure of textile construction or non-heat-insulating fire and smoke protection curtain in vertical installation position and closing direction.

FunctionSmoke protection closure of textile construction or non-thermally insulating fire and smoke protection closure
VerificationCE identification pursuant to EN 16034:2014 in conjunction with EN 13241:2003+A2:2016
Closing directionFrom top to bottom
Fire resistanceE 0 – EW 120 | tested in compliance with EN 1634-1:2014+A1:2018 | Classified according to EN 13501-2:2016
Smoke protectionSa, S200 | tested in compliance with EN 1634-3:2005-01 | classified according to EN 13501-2:2016
Closing cyclesC, C1, C2 | tested in compliance with EN 12605:2000-08 and EN 12604:2017-12 | classified according to EN 13501-2:2016
Fire behaviour of the fabricA2-s1, d0; B-s1, d0; E-d2 | tested in compliance with ISO 1716 and EN 13823 or ISO 11295-2 | classified according to EN 13501-1:2018
Environment conditionsSpecial environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.)
Visible surfacesgalvanized, RAL - smooth - silk gloss - standard shade, NCS - standard shade
Fiberseal

Legendary system components:
1 = Smoke detector
2 = Housing
3 = Guide rail
4 = Control module
5 = Release device (Details of the electrical components are to be taken from the valid general type approval of the hold-open system.)

Legal dimensioning:
Structure
B = Clear shell construction height
A = Clear shell construction width
System
AY = System height
LH = Clear system height
LB = Clear system width
BJ = Sstem width
Housing
BX = Depth
BW = Height
v = Offset between guide rail and housing
Guide rail
CD = Wwidth
CE = Depth
BD = Offset left
BD = Offset right

Structural system design (system drawing)

The combination of classifications or the ratio of clear system width to clear system height may reduce the stated maximum dimensions and the dimensions of the housing and guide rails may vary. The specifications on the quotation apply.

ClassificationSize max* [y x r] in mmFabricWall thickness** in mmHousingGuide rail
E 30, EW 307700 x 5000Heliotex 9150Type A, B, C, D, EType 1, 2
E 60, EW 607700 x 5000Heliotex 9150Type A, B, C, D, EType 1, 2
E 90, EW 907700 x 5000Heliotex 9150Type A, B, C, D, EType 1, 2
E1207700 x 5000Heliotex 9175Type A, B, C, D, EType 1, 2
E120, EW 1204340 x 2700Heliotex 9175Type A, B, C, D, EType 1, 2
C0, C17500 x 5000Protex 600 2S
C0, C1, C27002 x 4500Protex 1100 2S
C0, C1, C27500 x 5000Heliotex 9
Sa ***Joint length of 14.85 mProtex 600 2SType A, B, C, D, E
Sa ***Joint length of 14.85 mProtex 1100 2SType A, B, C, D, E
Sa ***Joint length of 14.85 mHeliotex 9Type A, B, C, D, E
S200 ****Surface 25.2 m2
Joint length of 20.1 m
Protex 600 2S
Protex 1100 2S
Heliotex 9

The installation situation must comply with the building regulations of the country of installation. The fire resistance of a ceiling or wall supporting structure and the adjoining components must correspond at least to that of the fire and / or smoke protection closure or that of the fire and / or smoke protection curtain. Proof of the stability and suitability for use of the adjacent walls and walls and components must be ensured under general ambient conditions and in the event of fire. See also notes on the standard supporting structure in EN1366-7:2004 and EN1363-1:2020. fire protection system must not be subjected to any additional load other than its own weight, even in the event of a fire
* Deviations from size dimensions on request
** tested wall types according to the installation instructions
*** normative: 3-sided without termination strip must not be exceeded!
**** normative: 4-sided must not be exceeded!

Housing


Fiberseal
Ceiling mounting
Typ A: BX = 285 mm, BW = 200 mm
Typ B: BX = 350 mm, BX = 260 mm
Typ C: BX = 190 mm, BW = 290 mm
Typ D: BX = 290 mm, BW = 360 mm
Typ E: BX = 380 mm, BW = 420 mm
Fiberseal
Wall mounting
Typ B: BX = 350 mm, BW = 260 mm
Typ C: BX = 190 mm, BW = 290 mm
Typ D: BX = 290 mm, BW = 360 mm
Typ E: BX = 380 mm, BW = 420 mm
Fiberseal
Wall mounting suspended ceiling with cover
Typ B: BX = 350 mm, BW = 260 mm
Typ C: BX = 190 mm, BW = 290 mm
Typ D: BX = 290 mm, BW = 360 mm
Typ E: BX = 380 mm, BW = 420 mm

Guide rails


Typ 1
Type 1 (Wall mounting)
CD = 104 mm
CE = 74 mm
BD/BE ≥ 0 mm
v = 0 mm
Typ 2
Type 2 (Embrasure mounting)
CD = 104 mm
CE = 74 mm
v = 0 mm
Typ 2
Type 2 (Niche mounting)
CD = 104 mm
CE = 74 mm
v = 0 mm

CDN = 120 mm
CEN = 100 mm

Note: Dotted line for the winding shaft receptacle (housing)