• EN
  • World market leader
  • Sustainability
  • Solutions
    • Fire protection curtains

      Fire protection curtains

      In case of fire, fire protection curtains close wall and ceiling openings. Their construction (roll-down or folding technique) and the use of different fabrics provide for a wide range of applications as well as different protection goals, classifications and time classes. The casing and guide rails of the highly flexible systems blend almost invisibly into the building and allow plenty of scope for sophisticated architecture and open room concepts.

    • Conveyor system closures

      Conveyor system closures

      Various production and logistics processes call for the most diverse types of conveyor systems. If these conveyor lines pass through fire-retardant or fire-resistant walls or ceilings, the openings required for this purpose must be provided with fire protection closures to prevent the spread of fire through the conveyor system or the goods conveyed. In the event of fire, conveyor system closures (CSC for short) must close these openings immediately and automatically. Fire resistance classified according to DIN EN 13501-2 is just as important as the smooth clearance of the closing areas in the event of a fire.

    • Smoke curtains

      Smoke curtains

      A smoke apron is a part of a smoke control system which also includes other components such as natural smoke and heat exhaust ventilators (EN 12101-2) and mechanical smoke and heat exhaust ventilators (EN 12101-3). Smoke aprons restrict the movement of combustion gases within a building in case of fire.

    • Smoke protection curtains

      Smoke protection curtains

      Once closed, smoke protection curtains (SPC) restrict the passage of smoke during the phase of fire formation, so that in the event of a fire, there is enough time to rescue people and animals from the room behind the curtain and to recover material assets without the need for respiratory equipment.

    • Tube sealings

      Tube sealings

      The solution for issues with fire protection dampers in ventilation and air conditioning systems in conveyor processes. Stöbich offers fire protection for pneumatic conveyor lines the closing elements of which are not exposed to the flow of conveyed material. This way, the closing element cannot be damaged or contaminated by abrasive conveyed goods.

    • Control units

      Control units

      Each automatic fire protection system needs a control unit. They are critical to safety, because a failure of this function means that the entire investment into a fire protection sealing has been in vain. Control units coordinate both fire detection and interaction with other control units, such as higher-level building control systems or clearing of the closing area of conveyor system closures.

  • References
  • Theme worlds
  • News
  • Contact

SUPERCOIL

Supercoil

Product description

Supercoil is outstanding for its flexibility in the implementation of made-to-measure solutions. The smoke apron consists of one web part up to 50 m in width and features a drop length of 9.5 m. It is designed for high time classes at temperature loads up to 600 0C (D) and 1,100°C (ETK curve - DH). If guide rails are used, the smoke apron ensures that zero smoke escapes over the entire width of the apron. Thanks to the 'Gravigen' drive motor the apron closes without external energy. Supercoil is also suitable as a floor-closing and partition-forming smoke apron and can be equipped with an opening that allows persons to pass. Furthermore, the clever design allows for a combination with the passable Stripecoil smoke apron.

TypeTextile smoke apron
Proof of usabilityCE according to DIN EN 12101-1 | UL 1784
FabricProtex 600.1 A2 | Protex 1100.1 A2
Verification0761-CPD-0060
Closing directionFrom top to bottom
Closing cycles1,000 cycles according to DIN EN 12101-1
ClassificationDH 120 | D 60 | Classification according to DIN EN 12101-1
TriggeringApproved hold-open system | To be provided on site

Constructive system design (with guide rail)

Supercoil

Legend System components:
1 = Smoke detector
2 = Casing
3 = Side guide
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release
11 = Wicket door (optional)

FabricSystem widt h(SB)Drop length (AL)t (mm)h (mm)
Protex 600.1 A2 / 1100.1 A2≥ 0,8 m - ≤ 1,6 m≤ 3,5 m190250
Protex 600.1 A2 / 1100.1 A2≥ 1,6 m - ≤ 30 m≤ 3,5 m190200
Protex 600.1 A2 / 1100.1 A2≥ 1,2 m - ≤ 30 m> 3,5 m - ≤ 6 m190250
Protex 1100.1 A2≥ 2,0 m - ≤ 20 m> 6 m - ≤ 9 m235290

Constructive system design (without guide rail)

Supercoil

Legend System components:
1 = Smoke detector
2 = Casing
4 = Fixing bracket
5 = Fabric
6 = Closing element
7 = Tubular motor
8 = Control module
9 = Control with operating unit
10 = Manual release

FabricSystem width (SB)Drop length (AL)t (mm)h (mm)
Protex 600.1 A2 / 1100.1 A2≥ 0,8 m - ≤ 1,6 m≤ 3,5 m190250
Protex 600.1 A2 / 1100.1 A2≥ 1,6 m - ≤ 50 m≤ 3,5 m190200
Protex 600.1 A2 / 1100.1 A2≥ 1,2 m - ≤ 50 m> 3,5 m - ≤ 6 m190250
Protex 1100.1 A2≥ 2,0 m - ≤ 50 m> 6 m - ≤ 9 m235290

Closing strips


Closing strips Fibershield-P
Standard
Typ 4,6
Closing strips Fibershield-P
Spring-loaded closing strip
Typ = 3,84 F (Special)
Closing strips Fibershield-P
Spring-loaded closing strip
Typ = 4,6 F (Special)

Casing installation options


Wall mounting
Wall mounting
Suspension mounting
Suspension mounting
Ceiling mounting
Ceiling mounting

Guide rails


Typ 105 E (niche)
Type 105 E (niche)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²
Typ 105 E (embrasure)
Type 105 E (embrasure)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²
Typ 105 E (Wall)
Type 105 E (Wall)
a = 105 mm
b = 74 mm

AL = ≤ 6 m
A = ≤ 50 m²


Typ 80 E
Type 80 E
a = 80 mm
b = 74 mm

AL = ≤ 3,5 m
A = ≤ 18 m²
Typ 160 E
Type 160 E
a = 160 mm
b = 100 mm

AL = ≤ 9 m